Home 02

Power Management System

   

EMS314

Power Meter with AMF & ATS

EMS860
EMS314
 
EMS314 integrates all the AC functions required for Telecom Genset applications. It provides Mains Metering, Genset Metering, AMF and ATS Control to supplement the basic engine controllers. It also provides high level of system protection, which is not available with conventional metering hence improving reliability and reducing system cost.
 
OVERALL SIZE
120mm x 100mm x 32mm
 
PANEL CUTOUT SIZE
92mm x 92mm
 
WEIGHT
145g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. EXPANSION MODULES
KEY FEATURES BENEFITS
Integrated solution for Telecom DG sets Integrated system
Dual Power Meter for DG and Mains Reduces system cost
Integrated AMF function Flexible
Integrated ATS controller  
Measures true RMS Volts, Current and Frequency.Class 1 accuracy  
Includes KW and KWH meters  
Includes Loading Gauge and Overload Protection  
Uses standard 5 amp CTs for current sensing. May be set to use 1 CT for balanced loads  

FEATURES

SPECIFICATIONS

Overall Dimensions

120 x 100 x 32mm

Mounting Hole

92 x 92mm. Mounted using 4 x M4 x 6mm plastic rivets

IP rating

IP66 front, IP20 rear

Supply Voltage

6V to 36V DC
Nominal 12V or 24V Automotive

Supply Current

Nominal 50mA

General protection

Reverse voltage, 120V load dump

Input Reference

0V DC/ Common

Mains Voltage Input Range

60-300 Volts RMS. Short duration overload capability 350V

Generator Voltage Input Range

60-300 Volts RMS. Short duration overload capability 350V

Mains Under/Over Frequency

Under Frequency = 40Hz, Over Frequency = 70Hz

Generator Under/Over Frequency

Under Frequency = 40Hz, Over Frequency = 70Hz

Output protection

Short circuit, reverse voltage, load dump, inductive relay currents.

Set-up and Adjustment

Menu buttons and LCD or by PC with cloning software.

Terminations

Screw less connections on rear. Recommended wire size 0.75mm

Operating Temperature

-10 to +70°C

Storage Temperature

-20 to +70°C

Relative Humidity

95% non condensing @ 50°C

Environmental Tests
EMC Compliance
Electrical Safety
Design
Manufacturing

IEC68 Part2
EN50081-1, EN50081-2, IEC6100-4-3
AS3100, AS3260
ISO 9001 
ISO 9002