Home 02

Power Management System

   

EMS316

Multistart Module

EMS860
EMS316
 

The EMS316 Multistart unit is used in the Celluar Telecom Sector for delaying the starting of the Genset after a mains fail until either the batteries need charging or the cell hut temperature require airconditioning.


Its purpose is to save fuel by running the Diesel Genset only when required.
It is a Din Rail mounted unit and can provide the front end moniroing for any Genset Controller with an autostart input.

 
OVERALL SIZE
41mm x 86mm x 40mm
 
PANEL CUTOUT SIZE
72mm Din Rail x 32mm (W)
 
WEIGHT
 30g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. EXPANSION MODULES
KEY FEATURES
LVM Input for mains AC status
Isolated battery voltage monitoring from 10 to 60 Volts
Genset starting and stopping on AMF, Aircon Status, low String battery
LED icons for AMF running status, Aircon Status and battery status
Output to control the Genset Run request
Fitted with serial port for communications
Fully configurable through the DIP switches.
Din rail mounted for easy installation
12V DC powered with low standby and operating current

FEATURES

SPECIFICATIONS

Overall Dimensions

41mm x 86mm x 40mm

Mounting Hole

Din Rail 72mm Series. 32mm rail

IP Rating

IP30

Supply Voltage

8V to 16V

Short Circuit Protection

Protected (Reverse Polarity Protection)

Supply Current

Standby : 5mA@12V DC power supply
Maximum: 120mA Depending on Fan out

Testing

Environmental Test: IEC68 Part2
EMS Compliance:EN50081-1, EN50081-2, IEC61000-4-3