Home 02

Auto Mains Failure Controllers

   

EMS375

Power Meter with AMF & ATS Controller Unit

EMS860
EMS375
 
EMS375 integrates all the functions required for Automatic Transfer Switch control in Diesel Genset applications. It provides Mains Metering, Genset Metering, AMF and ATS control to supplement the basic engine control. It also provides a high level of system protection, not available with conventional metering, improving reliability and reducing system cost.
 
OVERALL SIZE
100mm x 120mm x 32mm
 
PANEL CUTOUT SIZE
92mm x 92mm
 
WEIGHT
160g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. SIMILAR PRODUCTS
  4. EXPANSION MODULES
KEY FEATURES BENEFITS
Manual and Autostart with AMF initiated start and stop sequencing. Reduces system cost
Integrated solution for Automatic Staring Gensets. Integrated System
Dual Power Meter for Genset and Mains Overload Protection reduces warranty costs
Single or three phase operation Flexible
Integrated AMF function as well as ATS Controller  
LCD backlight for low light level viewing  
Protected solid-state outputs drive the external 12V control relays  
Mass Termination connectors for improved reliability  
Communications Port for remote monitoring.  

FEATURES

SPECIFICATIONS

Overall Dimensions

100 x 120 x 32mm

Mounting Hole

92 x 92mm Mounted using 4 x M4 x 6mm plastic rivets

IP rating

IP66 front, IP20 rear

Supply Voltage

8V to 16V DC
Nominal 12V Automotive

Operating Temperature

-20 to + 70 °C

Storage Temperature

-20 to + 70 °C

Relative Humidity

95% non-condensing @ 50°C

Supply Current

Nominal 50mA

General Protection

Reverse voltage, 120V load dump

Input Reference

0V DC/Common

Mains Voltage Input Range

60-300 Volts RMS. Short duration overload capacity 350V

Generator Voltage Input Range

60-300 Volts RMS. Short duration overload capacity 350V

Mains Under/Over Frequency

Under Frequency = 40Hz, Over Frequency = 70 Hz

Generator Under/Over Frequency

Under Frequency = 40Hz, Over Frequency = 70 Hz 

Output OP1 to OP5

Replay Coil Driver Open drain current limited 32V 300mA

Output protection

Short circuit, reverse voltage, load dump, inductive reply currents

Operating Temperature

-10 to +70°C

Storage Temperature

-20 to +70°C

Set-up and Adjustment

Menu buttons and LCD or by PC with cloning software

Terminations

Mass Termination. Recommendded wire size 0.75mm

Testing

Environmental Tests: IEC68 Part 2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260

Design ISO 9001, ISO9002