Remote Monitoring Solutions

   

EMS700

DataLogger

EMS700
 
The EMS700 data logger is a communication device which is intended to monitor ELTRAC (Single Phase / Multi Phase AC Meter) meters, site security, and other critical conditions. It gets all this information from ELTRAC meters through RS485 communication. It also has the ability to transfer this data to Remote server on request.
 
The collected data is then used to monitor and action, alarms and log these alarms in an internal memory.
 
OVERALL SIZE
180mm x 126mm x 51mm
 
PANEL CUTOUT SIZE
155mm x 117mm
 
WEIGHT
270g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. SIMILAR PRODUCTS
  4. EXPANSION MODULES
KEY FEATURES BENEFITS
Data logger and communications device Provides comprehensive real time knowledge of thenetwork supporting infrastructure.
Intended to monitor on site power sources, including Mains Power conditions, Diesel Generator performance, site security, and other critical site conditions. Improves fuel and service management.
Collected data is automatically transferred to a central server via GPRS Connectivity Provides immediate knowledge of infrastructure failure to ensure maximum availability.
Improves fuel and service management Improves network reliability.
Improves network reliability Provides automatic SMS messages to local service providers in the event of site failure.
Reduce network operating costs.

FEATURE

SPECIFICATIONS

Overall Dimensions

180 x 126 x 51mm

Mounting Hole

155 x 117mm

IP rating

IP56 front, IP20 rear

Supply Voltage

8 V to 36V DC

Nominal Automotive

Operating Temperature

-20 to +70°C

Storage Temperature

-20 to +70°C

Relative Humidity

95% non-condensing

Supply Current

Standby < 10mA

Running 70mA

AC Voltage Range

L-N = 350VRMS.

AC Frequency Range

40 – 70Hz

CT current range

0 – 5A + 25% Overload

Overall Accuracy

Class 1

Digital Output Rating

Open Drain Relay Coil Driver.  300mA 362VDC max.

Short Circuit protected.

Digital Input Rating

Opto-coupler isolated.

 Whetting current 10mA at 12 V DC.

DC input protection for +/- 30V DC

Transient Protected.

Analog Input Rating

Current limited outputs approx 15mA or less as required by sensors/

Short circuit and reverse voltage protected.

Input Reference

0V Common

Displayed Speed Range

0 – 4000 RPM

Engine Hours

0 – 99999.9 Hours

Kilo Watt Hours

0 – 999999.9 KWH

Oil Pressure Sensor Type

Switch: Close on fault

Resistive 10 to 180 Ohms (VDO/Datcon)

Oil Pressure Range

500, 750, 1000 KPa

Engine Temperature Sensor Type

Switch: Close on fault

Resistive (NTC)

Engine Temperature Range

VDO 120ºC, VDO 150ºC, VDO 200ºC

Canopy Temperature Sensor Type

Switch: Close on fault

Resistive (NTC)

Canopy Temperature Range

EMS08 0-100 ºC

Oil Temperature

Switch: Close on fault

Resistive (NTC)

Oil Temperature Range

40ºC-150ºC

Fuel Level Sensor Type

Switch: Close to fault

Resistive 0 to 90 Ohms

Resistive 10 to 180 Ohms

Resistive 180 to 10 Ohms

Battery Volts Measurement

8 to 36 Volts

Set-up and Adjustment

All features may be adjusted using set-up buttons and LCD menu or via a PC Windows based utility

Terminations

Amp DUAC / Molex Mini Fit JNR

Testing

Environmental Tests: IEC68 Part2

EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3

Electrical Safety AS 3100 and AS 3260