Home 02

Manual & Auto Start Controllers

   

EMS326

Genset Controller Unit

EMS326
 
EMS326 Genset Controller is designed for small gensets. The unit is comprised of manual and autostart initiated start and stop sequencing. The device monitors various parameters of the Engine and Alternator and also provides protection in a single integrated package.It also provides comprehensive monitoring of the Engine & Generator operating parameters and does automatic shutdown of the genset in the event of damaging conditions.
 
OVERALL SIZE
100mm x 120mm x 60mm
 
PANEL CUTOUT SIZE
92mm x 92mm
 
WEIGHT
160g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. SIMILAR PRODUCTS
  4. EXPANSION MODULES
KEY FEATURES BENEFITS
Manual and Autostart initiated start and stop sequencing. Reduces system cost
Provides engine and alternator protection by monitoring their parameters. Integrates engine gauges and AC metering into one unit.
Immediate alarm sensing and display Minimized control panel wiring reduces the material and labor costs
Fuel wastage reduction Reduces warranty costs by providing comprehensive engine and generator protection and a maintenance due timer.
Operational cost reduction Flexibility, the unit can be customized by PC cloning for individual genset model characteristics and fitments.
Stop alarm log shows last 50 stops for alarm and giving time and reason. Includes communications port for remote monitoring applications, dual station operation.

FEATURES

SPECIFICATIONS

Overall Dimensions

100 x 120 x 60mm

Mounting Hole

92 x 92mm

IP rating

IP55 front, IP20 rear

Supply Voltage

8V to 36V DC
Nominal Automotive

Operating Temperature

-20 to + 70 °C

Storage Temperature

-20 to + 70 °C

Relative Humidity

95% non-condensing

Supply Current

Standby <7mA
Running 50mA

AC Voltage Range

L-N = 350VRMS

AC Frequency Range

40 - 70Hz

CT current range

0 - 5A + 25% Overload

Overall Accuracy

Class 1

Digital Output Rating

Open Drain Relay Coil Driver. 300mA 32VDC max

Input Reference

0V Common

Displayed Speed Range

0 - 5000 RPM

Engine Hours

0 - 99999.9 Hours

Kilo Watt Hours

0 - 999999.9 KWH

Oil Pressure Sensor Type

Switch: Close on fault
Resistive

Oil Pressure Range

500, 750, 1000 KPa

Engine Temperature Sensor Type

Switch: Close on fault 
Resistive (NTC)

Canopy Temperature Sensor Type

Switch: Close on fault
Resistive (NTC)

Fuel Level Sensor Type

Switch: Close to fault
Resistive

Battery Volts Measurement

6 to 40 Volts

Set-up and Adjustment

All features can be adjusted using set-up buttons and LCD menu or via a PC Windows based utility

Terminations

Amp DUAC / Molex Mini Fit JNR

Testing

Environmental Tests: IEC68 Part 2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260