EMS363 Generator Controller Unit is a custom designed controller sold in private market segment. The unit incorporates both manually and autostart initiated start and stop sequencing, monitors engine and alternator operating parameters and provides both engine and alternator protection, in a single integrated package. Alarms and warnings are also shown on the LCD and supplemented by an alarm LED and Hooter output. The unit provides comprehensive monitoring of the engine and generator operating parameters and provides automatic shutdown of the set in the event of damagind conditions.
 
OVERALL SIZE
100mm x 120mm x 60mm
 
PANEL CUTOUT SIZE
92mm x 92mm
 
WEIGHT
115g
  1. PRODUCT HIGHLIGHTS
  2. TECHNICAL SPECIFICATIONS
  3. SIMILAR PRODUCTS
  4. EXPANSION MODULES
KEY FEATURES BENEFITS
Manual and Autostart initiated start and stop sequencing. Reduces system cost
Provides engine and alternator protection by monitoring their parameters. Integrates engine gauges and AC metering into one unit.
Automatic shutsdown of the genset in event of damaging conditons. Minimizes control panel wiring reduces the material and labor costs
Immediate alarm sensing and display Reduces warranty costs by providing comprehensive engine and generator protection and a maintenance due timer.
Fuel wastage reduction Flexibility, the unit can be customized by PC cloning for individual genset model characteristics and fitments.
Operational cost reduction Includes communications port for remote monitoring applications, dual station operation.

FEATURES

SPECIFICATIONS

Overall Dimensions

100 x 120 x 60mm

Mounting Hole

92 x 92mm

IP rating

IP55 front, IP20 rear

Supply Voltage

8V to 36V DC
Nominal Automotive

Operating Temperature

-20 to + 70 °C

Storage Temperature

-20 to + 70 °C

Relative Humidity

95% non-condensing

Supply Current

Standby  <7mA
Running 50mA

AC Voltage Range

L-N = 350VRMS

AC Frequency Range

40 - 70Hz

CT current range

0 - 5A + 25% Overload

Overall Accuracy

Class 1

Digital Output Rating

Open Drain Relay Coil Driver. 300mA 32VDC max

Input Reference

0V Common

Engine Hours

0 - 99999.9 Hours

Displayed Speed Range

0 - 5000 RPM

Fuel Level Sensor Type

Switch: Close to fault
Resistive 10 to 180 Ohms

Battery Volts Measurement

6 to 40 Volts

Set-up and Adjustment

All features can be adjusted using set-up buttons and LCD menu or via a PC Windows based utility

Terminations

Amp DUAC / Molex Mini Fit JNR

Testing

Environmental Tests: IEC68 Part 2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260